ASEA HLR 145245 E1 minimum oil, Nitrogen blanketed High Voltage breaker (02SUB, #902 2B138-2.82)
1 To allow switching (open/close) of a transmission line ( 2.82L) at 02SUB under normal operating conditions.
2 To allow isolation of a transmission line ( 2.82L) at 02SUB under a fault condition.
3 To provide easy access to making connections and overhauling various components inside the control cabinet.
4 To shield internal components in the control cabinet from elements of the environment.
5 To maintain the temperature inside the control cabinet to a minimum of 10 Deg C.
6 To reduce the humidity inside the control cabinet.
7 To allow selection of local / remote /disconnect electrical control of the breaker at the control cabinet.
8 To provide local electrical control of the breaker in the control cabinet.
9 To provide local mechanical control of the breaker in the control cabinet during maintenance.
10 To be capable of providing a local mechanical trip in the event of loss electrical opening capability.
11 To provide for slow closing/opening of the breaker for maintenance purposes.
12 To provide electrical isolation for the spring charging motor during maintenance.
13 To provide DC electrical isolation for the control and spring charging circuit.
14 To count the number of trip operations of the breaker.
15 To open the three poles simultaneously (is there a distance spec) within a time of 34 +/- 5 ms
16 To close the three poles simultaneously (is there a distance spec) within a time of 130 ms( range to be determined)
17 To shield internal components in the operating housing tube from elements of the environment.
18 To prevent contact with moving equipment in the opening spring housing
19 To provide access to the operating mechanism linkage for maintenance.
20 To transmit mechanical energy from the operating mechanism to the operating contact.
21 To insulate the energized components from ground at a rated voltage of 145 kV and to a BIL of 650 kV.
22 To support the interrupting chamber.
23 To contain all the insulating oil in the system.
24 To contain all of the nitrogen in the system up to a max of 0.7 mpa.
25 To release gases to the atmosphere to limit pressure in the interrupting chamber to less then 0.7 mpa.
26 To provide on/off (close/open) indication of the main contact.
27 To provide oil level indication in the interrupting chamber.
28 To provide gas pressure indication in the interrupting chamber.
29 To provide a grounding path independent of the support structure from the breaker to the ground grid.
30 To provide a grounding path from the support structure to the grounding grid.